Pramac - GE Zenith Controls Automatic Transfer Switches - UL Listed
ZTX series (MX-50 mircroprocessor with RM-4 as standard) UL
Listed / CDS / IEC
AG - ZTG series (MX-90 microprocessor with LCD interface and
NEMAR 3R as standard)
| Model |
Capacity Amps |
2 Pole - 120/240
Volts |
Nema 3R |
| ZTG15BS2M13 |
150 |
2068 |
INCLUDED |
| ZTG22BS2M13 |
225 |
2386 |
INCLUDED |
| ZTG40BS2M13 |
400 |
2848 |
INCLUDED |
| ZTG60BS2M13 |
600 |
5886 |
INCLUDED |
ZTG series (MX-100 microprocessor with module 13 as standard)
Accessories for ZTG three pole series:
MTS series 801 automatic transfer switches - NON UL Listed
Included Options:
| Under voltage sensing (90% pickup 80% dropout) of the utility
on any phase adjustable 190 to 500v |
| Voltage frequency sensing of the generator source set for 50
/ 60 Hz |
| Time delay engine start adjustable 0 to 60 seconds |
| Time delay engine warm up 10 seconds |
| Time delay utility (mains) stabilization / retransfer to
utility (mains) adjustable 0 to 4 minutes |
| Time delay engine cool down adjustable 0 to 4 minutes |
| Removable Key control 4 position: Off, Auto, Test, Run
Generator |
| Generator exerciser on - off every 7 days run for 15 minutes |
Westinghouse UL Listed three pole main line circuit