JOHN DEERE / DEUTZ POWERED RANGE - BASIC TIMERS

K/S 9700 AS 705 AS 730 Function Availabilty Factory Set
  X X Start Demand 0 - 10 Minutes 5 sec
  X X Engine Crank 03 - 59 secs 10 secs
  X X Start Attempts 1 - 9 attempts 3 attempts
  X X Overide Timer 02 - 59 secs 15 secs
X     Overide Timer <10 to>30 secs 15 secs
  X X Warm Up 
(gen. contactor)
00 - 59 secs 5 secs
  X X Mains Restore 0 - 1 hour 3 min
  X X Engine Cool 0 - 1 hour 3 min

JOHN DEERE / DEUTZ POWERED RANGE - ELECTRICAL OPTIONS

Indication Keystart Autostart 705 Autostart 730
Voltmeter S S S
7 Pos Voltmeter Selector Switch S S S
Ammeter S S S
4 Pos Ammeter Selector Switch S S S
Frequency Meter S S S
Hours Counter S S S
Battery Charger Ammeter Gauge S S S
Lub. Oil Pressure Gauge S S S
Coolant Temperature Gauge S S S
Emergency Stop Button S S S
Emergency Stop with Key O O O
Battery Charger and Controls O O O
Engine Heater & Controls O O O
Alternator Heater O O O
Electronic Governor O O O
Key switch Stop/Run/Start S - -
Key switch Off (Reset) Auto/Manual - S -
On/Page Select/Off - - S
3 Attempt Start - S S
Fail to Start - S S
Cool Down Timer - S S
Volt Free Contact for Common Fault O O S
Volt Free Contact for Gen. Running S S S
Audible Alarm - Panel Mounted O O O
Audbile Alarm - Loose O O O
Kilowatt Meter O O O
Battery Volt Meter O O S
Lub.Oil Temp Gauge O O O
Shut Down with Indication      
Low Lub. Oil Pressure S S S
High Coolant Temperature S S S
Overspeed O S S
Shut Down Options Requiring Inputs Maximum of 1 Maximum of 3 Maximum of 3
High Lub. Oil Temperature O O O
Low Coolant Level O O O
Over Frequency O S S
Under Frequency O S S
Over Voltage O O S
Under Voltage O O S
Combined Under / Over Voltage O O S
Overcurrent from Remote Relay O O S
Overcurrent from Breaker Tip O O S
Low Fuel Level O O O
Low Coolant Level O O O
Earth Leakage O O O

 
 

 